The bottom line displays the common alarm status. Based on the current alarm state, “OK”, “Low Alarm”,
“High Alarm”, or “High High Alarm” is displayed. The status reflects the alarm condition including user
settable time delays.
3.3.3 AUXILIARY MODULE STATUS SCREEN
To view this screen, press the DISP key from the Overall Alarm Status Screen.
Aux1:ok
Relays 1-8: 10000000
Aux2:ok
Relays 1-8: 00000001
The above display is for example only. Actual values will vary.
The status of the Auxiliary Relay module(s) is displayed. If only one Aux module is installed, then the
bottom 2 lines are blank.
“ok” means the Aux module is responding on the network.
The next line for each Aux module displays the individual status of each relay 1-8 installed on the Aux
module. From left to right for relays 1 to 8, a 1 indicates the relay is energized and a 0 indicates it is de-
energized.
3.3.4 ZONE ppm STATUS SCREEN
To view this screen, press the DISP key from the Auxiliary Status Screen.
z1 Hi/Av: 25(05)/ 3
z2 Hi/Av: 12(11)/ 5
z3 Hi/Av: 0(20)/ 0
z4 Hi/Av: 0(32)/ 0
The above display is for example only. Actual values will vary.
The ppm status is displayed for each zone. If there are more than 4 zones, then press the DISP key
to view the status of the remaining zones.
Each line starts with the zone number. The first value is the highest ppm recorded for that zone together
with the transmitter network address causing this value. The average value for the entire zone is
displayed at the end of the line. In the example above, zone 1 has a high of 25ppm caused by EC Gold
transmitter # 5. The average for the zone is 3 ppm.
3.3.5 mA MODULE STATUS SCREEN
To view this screen, press the DISP key from the Auxiliary Module Status Screen. This screen is only
displayed if at least one mA module is installed. If more than 4 zones have mA modules then
press the DISP key to view the remaining zone mA status.
z1:MaxmA:ok AvrgmA:ok
z2:MaxmA:ok AvrgmA:ok
z3:MaxmA:ok AvrgmA:ok
z4:MaxmA:ok AvrgmA:ok
The above display is for example only. Actual values will vary. Only mA modules for installed zones are
displayed.